Flow Measurement
Accurate compressed air flow measurement is fundamental for audits, control, and system optimization.
Measurement Technologies
Thermal Mass
The most common method for compressed air:
Temperature
sensor
│
═══════════════════[●]═══════════════════
Heated
element
│
┌────┴────┐
│ Control │
│ ΔT │
└─────────┘
Principle: Measures the energy required to maintain a constant temperature difference. Higher flow equals more cooling, more energy required.
| Advantage | Disadvantage |
|---|---|
| Measures mass flow directly | Sensitive to humidity |
| Wide range (100:1) | Sensitive to gas composition |
| Low pressure drop | Requires calibration |
| No moving parts | Moderate response time |
Vortex
Bluff body
│
═══════════════════[▼]═══════════════════
│
Vortices
○ ○
○ ○
○ ○
│
Pressure/piezo
sensor
Principle: A body breaks the flow creating vortices. Vortex frequency is proportional to velocity.
| Advantage | Disadvantage |
|---|---|
| Very robust | Requires minimum flow |
| Low maintenance | Sensitive to vibrations |
| Long-term stability | Straight runs required |
| Wide temperature range | Not for low flows |
Differential Pressure
P1 P2
▼ ▼
═══════[╳]═════════════
Orifice
plate
$$\Delta P = P_1 - P_2$$
$$Q \propto \sqrt{\Delta P}$$
| Advantage | Disadvantage |
|---|---|
| Economical | Limited range (4:1) |
| Simple | High permanent pressure drop |
| Well understood | Orifice wear |
| Easy verification | Sensitive to upstream conditions |
Ultrasonic (Time of Flight)
Transducer A
╱
═════════════╱═══════════════
╱
╱
═════════╱═════════════════
╱
Transducer B
Time A→B ≠ Time B→A (due to flow velocity)
| Advantage | Disadvantage |
|---|---|
| Non-invasive (clamp-on) | High cost |
| No pressure drop | Sensitive to deposits |
| Wide range | Critical installation |
| Bidirectional | Complex calibration |
Meter Selection
By Application
| Application | Recommended Technology |
|---|---|
| Temporary audit | Ultrasonic clamp-on |
| Permanent monitoring | Thermal mass insertion |
| Billing | Thermal mass inline |
| High temperature | Vortex |
| Wet gases | Vortex |
| Low flow | Thermal mass |
Selection Table
| Factor | Thermal Mass | Vortex | ΔP | Ultrasonic |
|---|---|---|---|---|
| Range | ★★★★★ | ★★★ | ★★ | ★★★★★ |
| Accuracy | ★★★★ | ★★★★ | ★★★ | ★★★★ |
| Cost | ★★★ | ★★★★ | ★★★★★ | ★★ |
| Installation | ★★★ | ★★★ | ★★★★ | ★★★★★ |
| Maintenance | ★★★★ | ★★★★★ | ★★★ | ★★★★ |
Installation
Straight Run Requirements
Elbows, valves, etc.
│
════════════════╪════════[M]════════════
│ │
├──10D───┤──5D──┤
│ │ │
Upstream Meter Downstream
| Upstream Disturbance | Straight Run Required |
|---|---|
| 90° elbow | 10-15 D |
| Two elbows in plane | 15-20 D |
| Partially open valve | 20-25 D |
| Reduction | 10-15 D |
| Expansion | 15-20 D |
| Compressor | 25-30 D |
D = Pipe internal diameter
Location in System
Dry Side vs. Wet Side:
Compressor ══> Aftercooler ══> Dryer ══> Distribution
│ │
Wet side Dry side
(avoid) (preferred)
| Location | Advantage | Disadvantage |
|---|---|---|
| After dryer | Dry air, stable reading | Doesn't include purge |
| Before dryer | Total flow | Humidity may affect |
| At each compressor | Individual control | Multiple meters |
| At header | Total flow produced | Includes internal leaks |
Units and Conversions
Reference Conditions
Standard conditions (SCFM, Nm³/h):
- Pressure: 1 atm (14.7 psia, 1.01325 bar)
- Temperature: Varies by standard
SCFM (US): 60°F (15.6°C)
Nm³/h (Europe): 0°C (32°F)
FAD: Conditions at compressor inlet
SCFM ↔ Nm³/h Conversion
- (approximate)
For exact conversion:
Correction for Conditions
Example:
- Measured: 1000 CFM at 100 psig, 100°F
- Corrected to standard (14.7 psia, 60°F):
Calibration and Verification
Calibration Frequency
| Meter Type | Recommended Interval |
|---|---|
| Thermal mass | Annual |
| Vortex | 2-3 years |
| ΔP with orifice | Annual (orifice inspection) |
| Ultrasonic | Annual |
Field Verification
| Method | Accuracy | Complexity |
|---|---|---|
| Comparison with another meter | ±2-5% | Low |
| Tank capacity method | ±5% | Medium |
| Pump-up test | ±3% | Medium |
| Accredited laboratory | ±0.5-1% | High |
Tank Method
- Isolate tank from system
- Depressurize tank
- Measure time to fill from to
- Calculate flow:
Where:
- = Tank volume (ft³)
- = Pressures (psia)
- = Time (minutes)
Common Errors
| Error | Consequence | Solution |
|---|---|---|
| Insufficient straight runs | Erroneous readings | Use flow conditioners |
| Meter on wet side | Drift, damage | Relocate after dryer |
| Incorrect units | Incomparable data | Standardize to SCFM or Nm³/h |
| No P/T compensation | Error up to 20% | Use compensated meter |
| Incorrect orientation | Measurement error | Follow manual |
Quick Verification
Compare measured flow with compressor's theoretical flow. If it differs by more than 20%, investigate meter installation or possible leaks in the system.