Flow Units
Flow (volume rate) determines the speed of work. This is where it gets complicated because air is compressible.
The Fundamental Problem
Air is compressible. 100 liters of air at 100 psig occupy only ~14 liters at atmospheric pressure.
When we talk about flow, we must specify at what conditions we're referring.
Flow at Standard Conditions
| Unit | Name | Reference conditions |
|---|---|---|
| scfm | Standard Cubic Feet per Minute | 14.7 psia, 68°F (20°C), 0% RH |
| Nm³/h | Normal cubic meter per hour | 1.013 bar, 32°F (0°C), 0% RH |
| Sm³/h | Standard cubic meter per hour | 1.013 bar, 59°F (15°C), 0% RH |
| sl/min | Standard liters per minute | 1.013 bar, 68°F (20°C), 65% RH |
Caution!
scfm and Nm³/h are NOT directly convertible because they use different reference temperatures.
Actual vs. Standard Flow
| Term | Meaning |
|---|---|
| SCFM | Flow converted to standard conditions |
| ACFM | ACTUAL flow at operating conditions |
| ICFM | Flow at compressor INLET |
| FAD | Free Air Delivery - "free" air flow |
The Conversion Equation
Example:
- 100 scfm compressor
- Operating at 100 psig and 95°F
100 scfm becomes only 13.5 cfm of actual flow in the pipe!
FAD (Free Air Delivery)
FAD is the most common measure for compressor capacity. It represents the free air flow the compressor can deliver.
To compare compressors
Always compare FAD under the same reference conditions.
Conversions
| From | To | Factor |
|---|---|---|
| 1 scfm | Nm³/h | × 1.609 |
| 1 scfm | l/s | × 0.472 |
| 1 l/s | scfm | × 2.12 |
| 1 m³/min | cfm | × 35.3 |